Wire Sizing Calculator Skip to main content
Electrical Free Pro Features Available

Wire Sizing Calculator - NEC Voltage Drop & Ampacity Tables

Find the Right AWG Wire Gauge for Any Electrical Run

A guided wire-sizing planning calculator that walks through load type, voltage, distance, ambient temperature, and conduit-fill derating prompts - then screens AWG rows for copper and aluminum against local 75°C table data and voltage-drop math.

Unlike simple voltage drop calculators, this tool keeps the source-boundary questions visible: Is this a continuous load? What are the actual terminal ratings? How hot is that attic? How many current-carrying conductors are in the raceway? Those answers must be verified against the adopted NEC edition, equipment listing, AHJ requirements, and qualified electrical review.

See side-by-side copper vs aluminum planning rows with voltage at the load end, rough material-cost estimates, and a visual circuit diagram. Use the result to prepare review notes, not as a permit, inspection, or installation decision.

Pro Tip: For runs over 100 feet, voltage drop usually matters more than ampacity. Always check both. A wire that passes ampacity at 150 feet may still deliver unacceptable voltage drop to your load.

PREVIEW All Pro features are currently free for a limited time. No license key required.

Wire Sizing Calculator
🛠️

Plan the Review

Open a source-aware checklist with tool, material, safety, permit, and qualified-review prompts.

Open Outbuilding Wiring Review Checklist →

How It Works

  1. Select Your Load

    Pick from common presets (EV charger, welder, subpanel, HVAC) or enter custom amps and voltage. The calculator applies local 125% planning multipliers for continuous, motor, EV-charger, and lighting rows; verify the governing NEC article before relying on them.

  2. Set Load Type & Distance

    Tell the calculator what kind of load you are feeding and enter the one-way distance from your panel to the equipment. Motor, continuous, and EV-charger circuits may have additional code and equipment requirements beyond this calculator.

  3. Configure Environment

    Set ambient temperature and conductor-count adjustment prompts. Hot attics, rooftops, and bundled conductors can require ampacity derating under NEC 310.15, but the actual correction depends on the adopted code and installation details.

  4. Review Derating Impact

    See exactly how temperature and conduit fill derating affect your wire capacity. The calculator shows the combined derating factor so you understand why a wire rated for 100A might only carry 73A in your conditions.

  5. Compare Copper vs Aluminum

    View side-by-side planning rows for both materials with wire size, voltage drop percentage, voltage at the load end, rough conduit sizing, and rough material cost.

  6. Check the Circuit Diagram

    A visual circuit diagram shows your panel voltage, wire run, and the voltage actually arriving at your equipment. Color-coded voltage drop indicators make it obvious if your run is marginal.

Built For

  • Licensed electricians screening branch-circuit and feeder inputs before adopted-code review
  • Homeowners planning garage, workshop, or detached shop wiring with long runs
  • Solar installers sizing DC and AC runs from panels to inverters and main panels
  • EV charger planning where EVSE listing, Article 625, load calculation, and AHJ review still control
  • Well pump circuits running 200+ feet from the house panel to a well house or pump
  • Long-distance runs to barns, outbuildings, pole buildings, and detached garages
  • Sub-panel feeder planning for additions, finished basements, or accessory dwelling units

Features & Capabilities

NEC 310.16 Ampacity Table Prompts

Built-in local ampacity rows from the NEC 310.16 75°C column for copper and aluminum conductors. Circuits 100A and smaller commonly require 60°C termination review under NEC 110.14(C).

Load Type Planning Multipliers

Applies local 125% planning multipliers for selected load types and keeps motor, EV, lighting, welder, equipment-listing, and Article-specific review gaps visible.

Temperature & Fill Derating Prompts

Local ambient-temperature and conductor-count adjustment prompts help frame review of NEC 310.15 correction and adjustment factors. Verify actual raceway and conductor count before design use.

Parallel Run Prompt

When a single run cannot satisfy the local calculator, the calculator can show parallel-run prompts (up to 4) and rough cost changes, with parallel termination and code-review warnings.

Circuit Diagram Visualization

Interactive SVG diagram shows your panel, wire run, and load with color-coded voltage drop. See exactly what voltage arrives at your equipment and whether your run is in the green, yellow, or red zone.

Total Material Cost Estimate

Calculates wire and conduit cost for both copper and aluminum. Choose between EMT, PVC Schedule 40, or rigid metallic conduit materials. See the total savings from aluminum at a glance.

Comparison

AWG Gauge Copper Ampacity (75°C) Aluminum Ampacity (75°C) Typical Use
14 AWG 20A N/A 15A lighting circuits
12 AWG 25A 20A 20A general-purpose receptacles
10 AWG 35A 30A 30A dryers, water heaters
8 AWG 50A 40A 40-50A ranges, sub-panels
6 AWG 65A 50A 60A sub-panels, large appliances
4 AWG 85A 65A 70-80A feeders
2 AWG 115A 90A 100A sub-panels
1/0 AWG 150A 120A 150A feeders
2/0 AWG 175A 135A 150-175A feeders
4/0 AWG 230A 180A 200A main service entrance

Assumptions

  • Ampacity rows use the NEC Table 310.16 75°C column; NEC 110.14(C) termination-temperature verification remains required, especially for circuits 100A and smaller.
  • Voltage drop uses K-factor approximations for copper and aluminum conductors with one-way distance.
  • Ambient temperature assumed at 30°C (86°F) unless user specifies otherwise.
  • Conduit-fill adjustment is represented by user-selected planning factors, not a complete Chapter 9 fill calculation.
  • Single-phase or three-phase calculations based on user selection; power factor assumed at 1.0 for voltage drop unless specified
  • Wire insulation/type, wet-location rating, cable assembly rules, and termination ratings are not verified.

Limitations

  • Does not account for harmonic currents on shared neutrals in three-phase, four-wire systems
  • Does not calculate short-circuit withstand ratings or fault current protection
  • Temperature derating for bundled cables in cable trays follows NEC 392 - not covered by this tool
  • Does not address medium-voltage conductor sizing (over 600V)
  • Aluminum conductor recommendations do not account for specific alloy differences (AA-8000 series vs. older alloys)
  • Voltage drop percentages are guidelines - NEC recommends but does not mandate the 3%/5% thresholds

References

  • NEC (NFPA 70) Article 310 - Conductors for General Wiring, Table 310.16
  • NEC Article 215.2(A)(4) and 210.19(A)(1) - Voltage Drop Recommendations (3% branch, 5% combined)
  • NEC 110.14(C) - Temperature Limitations at Terminations
  • IEEE Std 141 (Red Book) - Recommended Practice for Electric Power Distribution for Industrial Plants
  • Copper Development Association - Voltage Drop Calculator Methodology
  • NEC Table 310.15(C)(1) - Adjustment Factors for More Than 3 Current-Carrying Conductors

Frequently Asked Questions

The NEC recommends no more than 3% voltage drop on branch circuits and 5% total (feeder plus branch circuit combined). While this is a recommendation rather than a hard code requirement, exceeding these values can cause equipment to malfunction, lights to dim, and motors to overheat. Most electricians treat 3% as the target for any individual run.
Aluminum is a cost-effective choice for large feeders (typically 4 AWG and larger), such as 100A or 200A sub-panel feeds. You must upsize aluminum by approximately two gauges compared to copper and use anti-oxidant compound on all connections. Aluminum is not recommended for 15A and 20A branch circuits. Modern AA-8000 series aluminum is far more reliable than the older AA-1350 alloy that caused problems in the 1960s and 1970s.
NEC Chapter 9 conduit fill depends on the exact raceway, conductor insulation, equipment grounding conductor, and conductor mix. This calculator shows rough conduit prompts and derating inputs, but it is not a Chapter 9 fill calculation of record.
When ambient temperature is elevated or more than three current-carrying conductors share a raceway, allowable ampacity may need correction or adjustment under NEC 310.15. This calculator applies user-selected planning factors; verify the exact factors against the adopted code and installation.
The calculator applies local 125% planning multipliers for continuous, motor, EV-charger, and lighting rows. The correct code method depends on the load type, equipment listing, circuit article, and AHJ interpretation.
Most jurisdictions require a licensed electrician for new circuit installations, service upgrades, and commercial work. Some areas allow homeowners to pull permits for their own primary residence. Always check with your local building department before starting work. Even if permitted to do your own wiring, an inspection is typically required before energizing new circuits.
The calculator can show local feeder planning rows, but service and feeder sizing depends on termination ratings, conductor type, dwelling/service rules, OCPD, grounding, voltage drop, conduit fill, utility requirements, and AHJ review. Treat the result as a starting point for a licensed electrician.
EVSE circuits require review of the actual EVSE nameplate, breaker rating, continuous-load treatment, load calculation, conductor terminations, voltage drop, listing instructions, permit, utility, and AHJ requirements. Use this calculator only as an early screening prompt.
A 12 AWG copper branch-circuit run can become voltage-drop limited before it becomes ampacity limited, especially at 120V. The actual acceptable distance depends on load current, voltage, conductor type, termination rating, voltage-drop target, and equipment requirements. Use this calculator as a planning prompt, then verify the circuit with the adopted code and qualified review.
Disclaimer: This calculator provides estimates for educational and planning purposes only. Ampacities use the NEC 310.16 75°C column; circuits 100A and smaller generally default to the 60°C column under NEC 110.14(C) unless equipment terminations are listed and marked 75°C, so verify termination ratings. Wire sizing also depends on local codes, installation conditions, and specific equipment requirements. Always verify results with a licensed electrician and your local electrical inspector before purchasing materials or beginning installation.

Learn More

Electrical

How to Size Wire for Long Runs

Why voltage drop matters more than ampacity on long wire runs, how NEC derating works, copper vs aluminum tradeoffs, and the mistakes that fail inspection.

Electrical

Wiring a Detached Shop or Garage

How to plan detached-shop electrical conversations with load lists, subpanel prompts, feeder voltage drop, burial/code caveats, utility, AHJ, and qualified-review gaps.

Shops & Outbuildings

Why Your Outbuilding Motor Won't Start

How long wire runs can affect outbuilding motor starting, with voltage measurement, nameplate LRA, source impedance, starter, manufacturer, and qualified-review caveats.

Industrial

System Chain Analysis Guide: Read a Whole Machine as One Chain

How to walk a rotating-equipment system from electrical supply through motor, transmission, and driven equipment, find which link is the problem, and pick the right field measurement to take next. Companion to the System Chain Analyzer.

Shops & Outbuildings

Rosemount 3051 Decoder Guide: Read SAL and CD Model Codes Without Guessing

How to read supported Rosemount 3051SAL and 3051C model-code rows with context, seal, order, certification, configuration, and safety review gaps visible.

Electrical

Wire & Cable Type Guide: What the Letters Mean, the "-2" Wet Rating, and the 110.14(C) Termination Trap

Plain-language wire and cable marking reference. The T/H/HH/W/N/X letter system; why the "-2" suffix is a 90 C wet rating, not a version number; the NEC 110.14(C) rule that a 90 C conductor is still sized from the 60 or 75 C termination column; NM-B and UF-B taken from the 60 C column; the flexible-cord letters; and AC versus MC grounding. Companion to the Wire & Cable Type Decoder.

Electrical

NEC Conduit Fill Rules Explained

How NEC Chapter 9 conduit fill calculations work. Tables 1, 4, and 5 explained with examples for EMT, IMC, RMC, and mixed conductor types.

Electrical

How to Size a Transformer Using NEC Article 220

Step-by-step guide to transformer sizing using NEC Article 220 demand factors. Covers single-phase and three-phase service calculations with worked examples.

Electrical

EV Charger Installation: Panel Sizing, Wire Runs, and Load Management

Level 1 vs Level 2 EV charger comparison, circuit sizing with continuous load rules, panel capacity assessment, wire sizing for long runs, NEC 625.42 energy management, and time-of-use rate optimization.

Electrical

Residential Load Source Boundaries

Source-boundary guide for local residential service-load prompts, legacy 220.82/220.83 labels, adopted NEC review, equipment data, EVSE, utility, conductors, permits, and AHJ gaps.

Related Tools

Electrical Live

Can I Run This On That?

Check if your circuit breaker and wiring can handle a specific appliance. Enter breaker size, wire gauge, and load wattage for a pass/fail verdict based on NEC standards.

Electrical Live

Generator Sizing Calculator

What size generator do you need? Add your appliances and loads to calculate total running watts and starting surge. Get a recommended generator size with built-in headroom.

Electrical Live

Panel Load Study

Do you actually need a panel upgrade? Walk your breaker panel with NEC Article 220 demand factors. See connected load vs. calculated demand and test whether an EV charger, heat pump, or hot tub fits.