Wire Sizing Calculator - NEC Voltage Drop & Ampacity Tables
Find the Right AWG Wire Gauge for Any Electrical Run
A guided wire-sizing planning calculator that walks through load type, voltage, distance, ambient temperature, and conduit-fill derating prompts - then screens AWG rows for copper and aluminum against local 75°C table data and voltage-drop math.
Unlike simple voltage drop calculators, this tool keeps the source-boundary questions visible: Is this a continuous load? What are the actual terminal ratings? How hot is that attic? How many current-carrying conductors are in the raceway? Those answers must be verified against the adopted NEC edition, equipment listing, AHJ requirements, and qualified electrical review.
See side-by-side copper vs aluminum planning rows with voltage at the load end, rough material-cost estimates, and a visual circuit diagram. Use the result to prepare review notes, not as a permit, inspection, or installation decision.
Quick check whether your existing circuit can handle a new load before pulling wire
Load Checker →Check generator load and runtime before qualified transfer and feeder review
Generator Planning →Check conduit fill before you pull conductors - NEC Chapter 9 limits apply
Conduit Fill →Run a full panel load study to confirm your service has capacity for the new circuit
Panel Load Study →How It Works
-
Select Your Load
Pick from common presets (EV charger, welder, subpanel, HVAC) or enter custom amps and voltage. The calculator applies local 125% planning multipliers for continuous, motor, EV-charger, and lighting rows; verify the governing NEC article before relying on them.
-
Set Load Type & Distance
Tell the calculator what kind of load you are feeding and enter the one-way distance from your panel to the equipment. Motor, continuous, and EV-charger circuits may have additional code and equipment requirements beyond this calculator.
-
Configure Environment
Set ambient temperature and conductor-count adjustment prompts. Hot attics, rooftops, and bundled conductors can require ampacity derating under NEC 310.15, but the actual correction depends on the adopted code and installation details.
-
Review Derating Impact
See exactly how temperature and conduit fill derating affect your wire capacity. The calculator shows the combined derating factor so you understand why a wire rated for 100A might only carry 73A in your conditions.
-
Compare Copper vs Aluminum
View side-by-side planning rows for both materials with wire size, voltage drop percentage, voltage at the load end, rough conduit sizing, and rough material cost.
-
Check the Circuit Diagram
A visual circuit diagram shows your panel voltage, wire run, and the voltage actually arriving at your equipment. Color-coded voltage drop indicators make it obvious if your run is marginal.
Built For
- Licensed electricians screening branch-circuit and feeder inputs before adopted-code review
- Homeowners planning garage, workshop, or detached shop wiring with long runs
- Solar installers sizing DC and AC runs from panels to inverters and main panels
- EV charger planning where EVSE listing, Article 625, load calculation, and AHJ review still control
- Well pump circuits running 200+ feet from the house panel to a well house or pump
- Long-distance runs to barns, outbuildings, pole buildings, and detached garages
- Sub-panel feeder planning for additions, finished basements, or accessory dwelling units
Features & Capabilities
NEC 310.16 Ampacity Table Prompts
Built-in local ampacity rows from the NEC 310.16 75°C column for copper and aluminum conductors. Circuits 100A and smaller commonly require 60°C termination review under NEC 110.14(C).
Load Type Planning Multipliers
Applies local 125% planning multipliers for selected load types and keeps motor, EV, lighting, welder, equipment-listing, and Article-specific review gaps visible.
Temperature & Fill Derating Prompts
Local ambient-temperature and conductor-count adjustment prompts help frame review of NEC 310.15 correction and adjustment factors. Verify actual raceway and conductor count before design use.
Parallel Run Prompt
When a single run cannot satisfy the local calculator, the calculator can show parallel-run prompts (up to 4) and rough cost changes, with parallel termination and code-review warnings.
Circuit Diagram Visualization
Interactive SVG diagram shows your panel, wire run, and load with color-coded voltage drop. See exactly what voltage arrives at your equipment and whether your run is in the green, yellow, or red zone.
Total Material Cost Estimate
Calculates wire and conduit cost for both copper and aluminum. Choose between EMT, PVC Schedule 40, or rigid metallic conduit materials. See the total savings from aluminum at a glance.
Comparison
| AWG Gauge | Copper Ampacity (75°C) | Aluminum Ampacity (75°C) | Typical Use |
|---|---|---|---|
| 14 AWG | 20A | N/A | 15A lighting circuits |
| 12 AWG | 25A | 20A | 20A general-purpose receptacles |
| 10 AWG | 35A | 30A | 30A dryers, water heaters |
| 8 AWG | 50A | 40A | 40-50A ranges, sub-panels |
| 6 AWG | 65A | 50A | 60A sub-panels, large appliances |
| 4 AWG | 85A | 65A | 70-80A feeders |
| 2 AWG | 115A | 90A | 100A sub-panels |
| 1/0 AWG | 150A | 120A | 150A feeders |
| 2/0 AWG | 175A | 135A | 150-175A feeders |
| 4/0 AWG | 230A | 180A | 200A main service entrance |
Assumptions
- Ampacity rows use the NEC Table 310.16 75°C column; NEC 110.14(C) termination-temperature verification remains required, especially for circuits 100A and smaller.
- Voltage drop uses K-factor approximations for copper and aluminum conductors with one-way distance.
- Ambient temperature assumed at 30°C (86°F) unless user specifies otherwise.
- Conduit-fill adjustment is represented by user-selected planning factors, not a complete Chapter 9 fill calculation.
- Single-phase or three-phase calculations based on user selection; power factor assumed at 1.0 for voltage drop unless specified
- Wire insulation/type, wet-location rating, cable assembly rules, and termination ratings are not verified.
Limitations
- Does not account for harmonic currents on shared neutrals in three-phase, four-wire systems
- Does not calculate short-circuit withstand ratings or fault current protection
- Temperature derating for bundled cables in cable trays follows NEC 392 - not covered by this tool
- Does not address medium-voltage conductor sizing (over 600V)
- Aluminum conductor recommendations do not account for specific alloy differences (AA-8000 series vs. older alloys)
- Voltage drop percentages are guidelines - NEC recommends but does not mandate the 3%/5% thresholds
References
- NEC (NFPA 70) Article 310 - Conductors for General Wiring, Table 310.16
- NEC Article 215.2(A)(4) and 210.19(A)(1) - Voltage Drop Recommendations (3% branch, 5% combined)
- NEC 110.14(C) - Temperature Limitations at Terminations
- IEEE Std 141 (Red Book) - Recommended Practice for Electric Power Distribution for Industrial Plants
- Copper Development Association - Voltage Drop Calculator Methodology
- NEC Table 310.15(C)(1) - Adjustment Factors for More Than 3 Current-Carrying Conductors
Frequently Asked Questions
Learn More
How to Size Wire for Long Runs
Why voltage drop matters more than ampacity on long wire runs, how NEC derating works, copper vs aluminum tradeoffs, and the mistakes that fail inspection.
Wiring a Detached Shop or Garage
How to plan detached-shop electrical conversations with load lists, subpanel prompts, feeder voltage drop, burial/code caveats, utility, AHJ, and qualified-review gaps.
Why Your Outbuilding Motor Won't Start
How long wire runs can affect outbuilding motor starting, with voltage measurement, nameplate LRA, source impedance, starter, manufacturer, and qualified-review caveats.
System Chain Analysis Guide: Read a Whole Machine as One Chain
How to walk a rotating-equipment system from electrical supply through motor, transmission, and driven equipment, find which link is the problem, and pick the right field measurement to take next. Companion to the System Chain Analyzer.
Rosemount 3051 Decoder Guide: Read SAL and CD Model Codes Without Guessing
How to read supported Rosemount 3051SAL and 3051C model-code rows with context, seal, order, certification, configuration, and safety review gaps visible.
Wire & Cable Type Guide: What the Letters Mean, the "-2" Wet Rating, and the 110.14(C) Termination Trap
Plain-language wire and cable marking reference. The T/H/HH/W/N/X letter system; why the "-2" suffix is a 90 C wet rating, not a version number; the NEC 110.14(C) rule that a 90 C conductor is still sized from the 60 or 75 C termination column; NM-B and UF-B taken from the 60 C column; the flexible-cord letters; and AC versus MC grounding. Companion to the Wire & Cable Type Decoder.
NEC Conduit Fill Rules Explained
How NEC Chapter 9 conduit fill calculations work. Tables 1, 4, and 5 explained with examples for EMT, IMC, RMC, and mixed conductor types.
How to Size a Transformer Using NEC Article 220
Step-by-step guide to transformer sizing using NEC Article 220 demand factors. Covers single-phase and three-phase service calculations with worked examples.
EV Charger Installation: Panel Sizing, Wire Runs, and Load Management
Level 1 vs Level 2 EV charger comparison, circuit sizing with continuous load rules, panel capacity assessment, wire sizing for long runs, NEC 625.42 energy management, and time-of-use rate optimization.
Residential Load Source Boundaries
Source-boundary guide for local residential service-load prompts, legacy 220.82/220.83 labels, adopted NEC review, equipment data, EVSE, utility, conductors, permits, and AHJ gaps.
Related Tools
Can I Run This On That?
Check if your circuit breaker and wiring can handle a specific appliance. Enter breaker size, wire gauge, and load wattage for a pass/fail verdict based on NEC standards.
Generator Sizing Calculator
What size generator do you need? Add your appliances and loads to calculate total running watts and starting surge. Get a recommended generator size with built-in headroom.
Panel Load Study
Do you actually need a panel upgrade? Walk your breaker panel with NEC Article 220 demand factors. See connected load vs. calculated demand and test whether an EV charger, heat pump, or hot tub fits.